Schneider Power Supply Phaseo ABL7, ABL8_ Regulated Power Supply, 100-240V AC, 24V 3.1 A, single phase, Optimized_ [ABLS1A24031]

Schneider Power Supply Phaseo ABL7, ABL8_ Regulated Power Supply, 100-240V AC, 24V 3.1 A, single phase, Optimized_ [ABLS1A24031]

https://www.hsedubai.com/web/image/product.template/49561/image_1920?unique=7e7a051

Industrial Automation / Power Supply / Regulator

343.00 AED 343.0 AED 343.00 AED

343.00 AED

Not Available For Sale

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: usually 2-3 Business Days, once order is placed, actual lead time will be confirmed.

Attachments

This ABLS regulated switch mode power supply (SMPS) supplies direct current voltage. It has a rated input of 100V to 240V AC and 140 V to 340 V DC, a rated output current of 3,13A at 24V DC and a rated power output of 75W. It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water. It installs on omega rail or fixing by screw. Its width is 27mm, its height is 123,6mm, its depth is 102mm. It ensures a protection against overloads and short-circuits with automatic restart after the source of overload/short-circuit has been corrected. It weighs 0.220kg. It is a power supply for industrial use, rail mounting. It conforms to EN62368-1, ENIEC61010-1/2-201, ENIEC61204-3, EN61000-6-1/2/3/4, EN61000-3-2-3, UL62368-1, UL61010-2-201/-1-201, CSAC22.2No62368-1/No61010-2-201/No61010-1 standards, and certified by CE, CUL listed/recognized, RCM, CBscheme. The Acti9 iC60 range of Miniature Circuit Breakers is recommanded for its protection. The type of protection is 10A, C curve or 13A, B-curve. It has in the front face a LED indicating presence of DC output voltage, and a QR code for access to the latest technical documentation. Thanks to its book housing, it can be installed either in enclosures or industrial panels by clipping on omega (DIN) rail. It brings energy to your automated systems. Designed for simple machines and applications, modular power supplies are primarily appreciated for their extreme compactness._ [ABLS1A24031]

Specifications

Main

Range of productModicon Power Supply
Product or component typePower supply
Power supply typeRegulated switch mode
Variant optionOptimized
Enclosure materialPlastic
Nominal input voltage100...240 V AC single phase
100...240 V AC 2 phases
140...340 V DC
Rated power in W75 W
output voltage24 V DC
Power supply output current3.13 A

Complementary

Input voltage limits85...264 V AC (without temperature derating)
120...375 V DC (without temperature derating)
85…120 V DC (with temperature derating)
Nominal network frequency50…60 Hz
Network system compatibilityTN
TT
IT
maximum leakage current1 mA 240 V AC
input protection typeIntegrated fuse (not interchangeable) 5 A
External protection (recommended) 20 A Curve C
External protection (recommended) 13 A Curve B
External protection (recommended) 10 A Curve C
inrush current40.0 A at 115 V
80.0 A at 230 V
power factor0.55 at 115 V AC
0.45 at 230 V AC
efficiency88 % at 230 V AC
Output voltage adjustment21.6...26.4 V
Power dissipation in W15 W
current consumption< 1.8 A 115 V AC
< 1 A 230 V AC
< 0.8 A 140 V DC
Turn-on time< 1.2 s
holding time> 20 ms 115 V AC
> 40 ms 230 V AC
Startup with capacitive loads5000 µF
Residual ripple< 120 mV
Expected capacitor life time10 year(s)
meantime between failure [MTBF]700000 h at 25 °C, full load conforming to SR 332
output protection typeAgainst overload and short-circuits, protection technology: automatic reset
Against over temperature, protection technology: manual reset
Against overvoltage, protection technology: manual reset
connections - terminalsScrew connection: 0.5...2.5 mm², (AWG 20...AWG 14) for output
Screw connection: 0.75...2.5 mm², (AWG 18...AWG 14) for input
line and load regulation< 0.5 % network 0 to 100 % load at 25 °C
< 1 % network full voltage range in line at 25 °C
status LED1 LED (green) output voltage
Depth102 mm
Height123.6 mm
Width27 mm
Product weight0.22 kg
Output couplingParallel
Serial
mounting supportTop hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Double-profile DIN rail
supplySELV conforming to EN/IEC 60950-1
SELV conforming to EN/IEC 60204-1
SELV conforming to IEC 60364-4-41
dielectric strength3000 V AC with input to output

Environment

StandardsEN 62368-1
EN/IEC 61010-1
EN 61010-2-201
EN/IEC 61204-3
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
EN 61000-3-2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
EN/IEC 62368-1
product certificationsCE
CUL listed
CUL recognized
RCM
CB Scheme
EAC
KC
NEC: class 2
environmental characteristic3M4 conforming to IEC 60721-3-3
operating altitude< 5000 m
shock resistance100 m/s² for 11 ms
IP degree of protectionIP20
Ambient air temperature for operation-20…-10 °C with current derating of 1 % per °C mounting position A < 2000 m
-10…40 °C without derating mounting position A 115 V AC < 2000 m
-10…50 °C without derating mounting position A 230 V AC < 2000 m
40…70 °C with current derating of 1.67 % per °C mounting position A 115 V AC < 2000 m
50…70 °C with current derating of 2.5 % per °C mounting position A 230 V AC < 2000 m
electrical shock protection classClass I
Pollution degree2
vibration resistance3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6
10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
Electromagnetic immunityImmunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/IEC 61000-4-2
Immunity to conducted RF disturbances - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 3 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3
Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4
Surge immunity test - test level: 3 kV (between power supply and earth) conforming to EN/IEC 61000-4-5
Surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8
Immunity to voltage dips conforming to EN/IEC 61000-4-11
Disturbing field emission conforming to EN 55016-2-3
Limits for harmonic current emissions conforming to EN 61000-3-2
Conducted disturbance emission conforming to EN 55016-1-2
Conducted disturbance emission conforming to EN 55016-2-1
electromagnetic emissionConducted emissions conforming to EN 61000-6-3
Radiated emissions conforming to EN 61000-6-4