Schneider Transformer Phaseo ABT7, ABL6_ voltage transformer - 230..400 V - 1 x 24 V - 100 VA_ [ABL6TS10B]

Schneider Transformer Phaseo ABT7, ABL6_ voltage transformer - 230..400 V - 1 x 24 V - 100 VA_ [ABL6TS10B]

https://www.hsedubai.com/web/image/product.template/43446/image_1920?unique=af306e9

Industrial Automation / Transformer / Voltage Transformer

749.00 AED 749.0 AED 749.00 AED

749.00 AED

Not Available For Sale

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: usually 2-3 Business Days, once order is placed, actual lead time will be confirmed.

Attachments

DISCONTINUED

This ABL6 transformer supplies alternating current to control circuits while isolating them from mains power. It has a rated input voltage of 230V to 400V AC, a rated output voltage of 24V AC and a rated power of 100VA. It offers an economic way to supply each consuming load individually, or by groups of loads, in applications such as mining, refining. It is ideal for systems accepting low voltage AC power, such as motor protection relays, contactors._ [ABL6TS10B]

Specifications

Main

Range of productModicon Transformer Optimized
Product or component typeSafety and isolation transformer
Rated power in VA100 VA
input voltage230 V AC single phase, terminal(s): N-L1
400 V AC phase to phase, terminal(s): L1-L2
output voltage24 V AC
Secondary windingSingle
Protective coverWithout
Ambient air temperature for operation-20…50 °C

Complementary

Input voltage limits207...253 V
360...440 V
Network frequency limits47…63 Hz
Input voltage tolerance+/- 15 V
Efficiency86 %
Power dissipation in W16.3 W
output sustained overvoltage9 % (no load, hot state)
Maximum voltage drop at rated load0 %
No load losses7.1 W
Short-circuit voltage0,0786
output protection typeAgainst overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
connections - terminalsFor input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11
For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11
For output connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 11
MarkingCE
fixing modeBy 4 screws diameter: 4.8 mm on vertical panel, operating position: horizontal
By 4 screws diameter: 4.8 mm on vertical panel, operating position: vertical
By clips (with mounting plate) on 35 mm symmetrical DIN rail
By 4 screws diameter: 4.8 mm on horizontal panel with derating to 90 %
Operating altitude3000 m
Electrical insulation classClass B
Width84.0 mm
Height87.0 mm
Depth95.0 mm
Net weight2.05 kg