Schneider Soft Starter Altistart 22_ soft Starter-ATS22-control 220V-power 230V(39kW)/400...440V(55kW)_ [ATS22C11Q]

Schneider Soft Starter Altistart 22_ soft Starter-ATS22-control 220V-power 230V(39kW)/400...440V(55kW)_ [ATS22C11Q]

https://www.hsedubai.com/web/image/product.template/72025/image_1920?unique=af948c4

Industrial Automation / Soft Starter / Soft Starter

4,732.00 AED 4732.0 AED 4,732.00 AED

4,732.00 AED

Not Available For Sale

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: usually 2-3 Business Days, once order is placed, actual lead time will be confirmed.

Attachments

This Altistart 22 soft Starter can feed 3-phase asynchronous motors in supply line or delta connection. It has a rating of 110A and 230V to 440V, a rated power up to 55kW (400V to 440V in supply line) and up to 90kW (400V to 440V in motor delta connection). It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility; allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life._ [ATS22C11Q]

Specifications

Main

Range of productAltistart 22
Product or component typeSoft starter
Product destinationAsynchronous motors
Product specific applicationPumps and fans
Component nameATS22
Network number of phases3 phases
[Us] rated supply voltage230...440 V - 15...10 %
motor power kW39 kW 230 V
55 kW 400 V
55 kW 440 V
Factory setting current100 A
power dissipation in W73 W for standard applications
Utilisation categoryAC-53A
Type of startStart with torque control (current limited to 3.5 In)
IcL starter rating110 A for connection in the motor supply line for standard applications
IP degree of protectionIP20

Complementary

Assembly styleWith heat sink
Function availableInternal bypass
Supply voltage limits195…484 V
supply frequency50...60 Hz - 10...10 %
Network frequency45...66 Hz
Device connectionIn the motor supply line
To the motor delta terminals
[Uc] control circuit voltage230 V - 15...10 % 50/60 Hz
Control circuit consumption20 W
Discrete output number2
discrete output typeRelay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
minimum switching current100 mA at 12 V DC (relay outputs)
maximum switching current5 A 250 V AC resistive 1 relay outputs
5 A 30 V DC resistive 1 relay outputs
2 A 250 V AC inductive 0.4 20 ms relay outputs
2 A 30 V DC inductive 7 ms relay outputs
Discrete input number3
discrete input type(LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
discrete input voltage24 V <= 30 V
discrete input logicPositive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
output current0.4...1 Icl adjustable
PTC probe input750 Ohm
Communication port protocolModbus
connector type1 RJ45
Communication data linkSerial
Physical interfaceRS485 multidrop
Transmission rate4800, 9600 or 19200 bps
Installed device31
protection typePhase failure: line
Thermal protection: motor
Thermal protection: starter
MarkingCE
Type of coolingForced convection
Operating positionVertical +/- 10 degree
Height356 mm
Width150 mm
Depth229.5 mm
Net weight18 kg
Motor power range AC-330…50 kW at 200…240 V 3 phases
55…100 kW at 380…440 V 3 phases
Motor starter typeSoft starter

Environment

electromagnetic compatibilityConducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
StandardsEN/IEC 60947-4-2
Product certificationsUL
CSA
GOST
C-Tick
CCC
vibration resistance1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f= 2…13 Hz) conforming to EN/IEC 60068-2-6
shock resistance15 gn for 11 ms conforming to EN/IEC 60068-2-27
Noise level56 dB
pollution degreeLevel 2 conforming to IEC 60664-1
relative humidity0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
ambient air temperature for operation-10…40 °C (without derating)
40…60 °C (with current derating 2.2 % per °C)
Ambient air temperature for storage-25…70 °C
operating altitude<= 1000 m without derating
> 1000...< 2000 m with current derating of 2.2 % per additional 100 m