Schneider Breaker Compact NSX <630_ circuit Breaker Compact NSX160F - TMD - 160 A - 4 poles 3d_ [LV430640]

Schneider Breaker Compact NSX <630_ circuit Breaker Compact NSX160F - TMD - 160 A - 4 poles 3d_ [LV430640]

https://www.hsedubai.com/web/image/product.template/72829/image_1920?unique=10f3a5d

Electrical / Breaker / MCCB

928.00 AED 928.0 AED 928.00 AED

928.00 AED

Not Available For Sale

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: usually 2-3 Business Days, once order is placed, actual lead time will be confirmed.

Attachments

This Compact NSX160F is a complete 4P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 160A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX160F is part of Schneider Electric EcoStruxure Power architecture.


Specifications

Main

rangeComPact
product nameComPact NSX
range of productComPact NSX100...250
device short nameNSX160F
product or component typeCircuit breaker
device applicationDistribution
Number of poles4P
protected poles description3t
neutral positionLeft
[In] rated current160 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
network typeAC
network frequency50/60 Hz
suitability for isolationYes conforming to EN/IEC 60947-2
utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity10 kA at 600 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelF 36 kA 415 V AC
trip unit nameTM-D
trip unit technologyThermal-magnetic
trip unit protection functionsLI
control typeToggle
Circuit breaker mounting modeFixed

Complementary

[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability40000 cycles
electrical durability7500 cycles at 690 V In
15000 cycles at 690 V In/2
20000 cycles at 440 V In
40000 cycles at 440 V In/2
mounting supportBackplate
upside connectionFront
downside connectionFront
connection pitch35 mm
protection typeL : for overload protection (thermal)
I : for short-circuit protection (magnetic)
trip unit rating160 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In
15 s at 6 x Ir
Short-time protection pick-up adjustment type IsdFixed
[Isd] Short-time protection pick-up adjustment range1250 A
Short-time protection delay adjustment type tsdFixed
earth-leakage protectionWithout
Neutral protection settingsNo protection (3t)
Number of slots for electrical auxiliaries5 slot(s)
Width (W)140 mm
Height (H)161 mm
Depth (D)86 mm
Net weight2.6 kg

Environment

StandardsEN/IEC 60947
product certificationsCCC
EAC
Marine
overvoltage categoryClass II
electrical shock protection classClass II
pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
relative humidity0…95 %
operating altitude0...2000 m without derating
2000 m...5000 m with derating

Packing Units

Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height14.4 cm
Package 1 Width15.2 cm
Package 1 Length19.2 cm
Package 1 Weight2.371 kg
Unit Type of Package 2S04
Number of Units in Package 29
Package 2 Height30.0 cm
Package 2 Width40.0 cm
Package 2 Length60.0 cm
Package 2 Weight22.105 kg