Schneider Breaker EasyPact EZC_ circuit Breaker Easypact EZC250H - TMD - 150 A - 4 poles 3d_ [EZC250H4150]
Electrical / Breaker / MCCB
Specifications
Main
range of product | EasyPact |
---|---|
product or component type | Circuit breaker |
device short name | Easypact EZC250H |
circuit breaker name | Easypact EZC250H |
device application | Distribution |
poles description | 4P |
protected poles description | 3t |
network type | DC AC |
network frequency | 50/60 Hz |
[In] rated current | 150 A at 40 °C |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2 |
breaking capacity code | H |
breaking capacity | 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | 5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | Yes conforming to IEC 60947-2 |
utilisation category | Category A |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic |
trip unit rating | 150 A at 50 °C |
protection type | Overload protection Short-circuit protection |
pollution degree | 3 conforming to IEC 60947 |
Complementary
control type | Toggle |
---|---|
mounting mode | Fixed |
mounting support | Backplate |
upside connection | Front |
downside connection | Front |
mechanical durability | 10000 cycles |
electrical durability | Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 |
connection pitch | 35 mm |
local signalling | Positive contact indication |
neutral protection setting | Without protection |
earth-leakage protection | Without |
Height | 165 mm |
width | 140 mm |
Depth | 60 mm |
Environment
Standards | JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1 |
---|---|
IP degree of protection | IP20 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to EN 50102 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -35…85 °C |
Packing Units
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 11.4 cm |
Package 1 Width | 11.3 cm |
Package 1 Length | 18.0 cm |
Package 1 Weight | 2.24 kg |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 6 |
Package 2 Height | 30.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 13.927 kg |