Schneider Power Supply Phaseo ABT7, ABL6_ battery control module - 24..28.8 V DC - 24 V - 20 A - for regulated SMPS_ [ABL8BBU24200]
Industrial Automation / Power Supply / Power Supply Accessories
This ABL8 battery control module supplies direct current voltage. It has a rated input of 24V to 28.8V DC, a rated output current of 20A at 24V DC. This battery control module is designed to act as a battery charger, to allow batteries usage during significant network power shortages. It has control backup battery charging and backup supply to ensure the longest battery life-time. It provides reliable and fast switching between network supply and battery supply avoiding disturbances on your critical control power supply lines. It weighs 0.500kg. It is a functionnal module for power supply for industrial use, rail mounting. It conforms to UL 508, CSA C22.2 No 60950-1 standards. It is certified by EAC, RCM. This functional module is mainly compatible with Modicon ABL8RP and Modicon ABL8WP Universal power supplies. It has LED diagnostics indicator available in the front for troubleshooting instantly. It installs on DIN rail. It brings energy to your automated systems. Designed for simple machines and applications, modular power supplies are primarily appreciated for their extreme compactness._ [ABL8BBU24200]
Specifications
Main
Range of product | Phaseo |
---|---|
Product or component type | Battery control module |
input voltage | 24...28.8 V DC |
output voltage | (Ubattery-0.5) V in battery mode DC (Uin-0.25) V in nominal mode DC |
maximum output current | 20 A |
Complementary
Input voltage limits | 22...30 V |
---|---|
Maximum power dissipation in W | 7 W |
Activation threshold | Adjustable 22...36 V |
Number of output channels | 1 |
current consumption | 0.6 A on load 0.1 mA no load <= 40.6 A |
output protection type | Against overload, protection technology: 1.5 x In Against short-circuits, protection technology: battery-backed mode, automatic reset Against short-circuits, protection technology: power-supplied mode |
connections - terminals | For diagnostic relay: removable screw terminal block, connection capacity: 1 x 0.75 mm² For input connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8 For output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8 |
fixing mode | By clips on 35 mm symmetrical DIN rail, operating position: horizontal By clips on 35 mm symmetrical DIN rail, operating position: vertical |
Operating altitude | 2000 m |
Marking | CE |
name of test | Electrostatic discharges conforming to EN/IEC 61000-4-2 Emission conforming to EN 61000-6-3 Induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3 Radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3 Rapid transient conforming to IEC 61000-4-4 level 3 Surge conforming to EN/IEC 61000-4-5 level 2 Conducted/radiated emissions conforming to EN 55022 class B, 20 % |
local signalling | 1 C/O relay for alarm status 1 C/O relay for battery status 1 C/O relay for power supply status LCD screen for module status |
Width | 60 mm |
Height | 125 mm |
Depth | 160 mm |
Net weight | 0.5 kg |
Environment
Product certifications | RCM EAC |
---|---|
Standards | UL 508 CSA C22.2 No 60950-1 |
Ambient air temperature for operation | -25…60 °C |
Ambient air temperature for storage | -40…85 °C |
environmental characteristic | EMC conforming to EN 61000-6-3 EMC conforming to EN/IEC 61000-6-2 Safety conforming to EN/IEC 60950-1 Safety conforming to EN/IEC 61204-3 |
IP degree of protection | IP20 conforming to EN/IEC 60529 |
dielectric strength | 500 V between input and ground 500 V between output and ground |
overvoltage category | Class II conforming to VDE 0106-1 |
relative humidity | 0…90 % during operation 0…95 % during storage |
MTBF reliability | 718708 H at 24 V DC with UTE C80-810 calculation method |
vibration resistance | 2 gn (f= 11.9…150 Hz) conforming to EN/IEC 61131-2 3.5 mm (f= 3…11.9 Hz) conforming to EN/IEC 61131-2 |