TeSys GV motor circuit breaker, 3 poles (3P), 4A/690V, for 3-phase motor applications 1.1-1.5kW@400V. It provides a thermal-magnetic protection with a thermal setting range 2.5-4A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).


Specifications

Main

rangeTeSys Deca
TeSys Deca
product nameTeSys GV2
TeSys Deca
product or component typeMotor circuit breaker
device short nameGV2P
device applicationMotor protection
trip unit technologyThermal-magnetic

Complementary

poles description3P
network typeAC
utilisation categoryAC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency50/60 Hz conforming to IEC 60947-4-1
motor power kW1.1 kW at 400/415 V AC 50/60 Hz
1.5 kW at 500 V AC 50/60 Hz
2.2 kW at 690 V AC 50/60 Hz
breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
control typeRotary handle
[In] rated current4 A
magnetic tripping current51 A
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current4 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
power dissipation per pole2.5 W
mechanical durability100000 cycles
electrical durability100000 cycles for AC-3 at 415 V
rated dutyContinuous conforming to IEC 60947-4-1
phase failure sensitivityYes conforming to IEC 60947-4-1
suitability for isolationYes conforming to IEC 60947-1 § 7-1-6
width45 mm
Height89 mm
Depth97 mm

Environment

StandardsEN/IEC 60947-2
EN/IEC 60947-4-1
product certificationsCCC
UL
CSA
EAC
ATEX
BV
LROS (Lloyds register of shipping)
UKCA
DNV-GL
RINA
IP degree of protectionIP20 conforming to IEC 60529
climatic withstandConforming to IACS E10
Ambient air temperature for storage-40…80 °C
fire resistance960 °C conforming to IEC 60695-2-11
ambient air temperature for operation-20…60 °C
operating altitude2000 m

Packing Units

Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height5 cm
Package 1 Width9.5 cm
Package 1 Length10 cm
Package 1 Weight329 g
Unit Type of Package 2S02
Number of Units in Package 220
Package 2 Height15 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight6.978 kg
Unit Type of Package 3P06
Number of Units in Package 3320
Package 3 Height75 cm
Package 3 Width80 cm
Package 3 Length60 cm
Package 3 Weight119.648 kg