Schneider Breaker TeSys GV2_ Motor circuit breaker, TeSys GV2, 3P, 17-23 A, thermal magnetic, screw clamp terminals_ [GV2ME21]

Schneider Breaker TeSys GV2_ Motor circuit breaker, TeSys GV2, 3P, 17-23 A, thermal magnetic, screw clamp terminals_ [GV2ME21]

https://www.hsedubai.com/web/image/product.template/72971/image_1920?unique=1de54e5

Electrical / Breaker / MPCB

166.13 AED 166.13 AED 166.13 AED

166.13 AED

Not Available For Sale

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: usually 2-3 Business Days, once order is placed, actual lead time will be confirmed.

Attachments

TeSys GV motor circuit breaker, 3 poles (3P), 23A/690V, for 3-phase motor applications 9kW@400V. It provides a thermal-magnetic protection with a thermal setting range 17-23A, magnetic tripping at 13xIn, high breaking capacity Icu 15kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).


Specifications

Main

rangeTeSys Deca
TeSys Deca
product nameTeSys GV2
TeSys Deca
product or component typeMotor circuit breaker
device short nameGV2ME
device applicationMotor protection
trip unit technologyThermal-magnetic

Complementary

poles description3P
network typeAC
utilisation categoryAC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency50/60 Hz conforming to IEC 60947-4-1
motor power kW9 kW at 400/415 V AC 50/60 Hz
11 kW at 500 V AC 50/60 Hz
18.5 kW at 690 V AC 50/60 Hz
breaking capacity3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
40 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
control typePush-button
[In] rated current23 A
magnetic tripping current327 A
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current23 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
power dissipation per pole2.5 W
mechanical durability100000 cycles
electrical durability100000 cycles for AC-3 at 415 V
rated dutyContinuous conforming to IEC 60947-4-1
phase failure sensitivityYes conforming to IEC 60947-4-1
suitability for isolationYes conforming to IEC 60947-1 § 7-1-6
width45 mm
Height89 mm
Depth78.5 mm
Net weight0.26 kg

Environment

StandardsEN/IEC 60947-2
EN/IEC 60947-4-1
product certificationsCCC
UL
CSA
EAC
ATEX
BV
LROS (Lloyds register of shipping)
UKCA
DNV-GL
RINA
IP degree of protectionIP20 conforming to IEC 60529
climatic withstandConforming to IACS E10
Ambient air temperature for storage-40…80 °C
fire resistance960 °C conforming to IEC 60695-2-11
ambient air temperature for operation-20…60 °C
operating altitude2000 m

Packing Units

Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height4.5 cm
Package 1 Width8.5 cm
Package 1 Length9.5 cm
Package 1 Weight290 g
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Height15 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight7.203 kg
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Height75 cm
Package 3 Width80 cm
Package 3 Length60 cm
Package 3 Weight123.248 kg