Schneider Breaker TeSys GV3_ Motor circuit breaker, TeSys GV3, 3P, 48-65 A, thermal magnetic, EverLink terminals_ [GV3P65]

Schneider Breaker TeSys GV3_ Motor circuit breaker, TeSys GV3, 3P, 48-65 A, thermal magnetic, EverLink terminals_ [GV3P65]

https://www.hsedubai.com/web/image/product.template/72897/image_1920?unique=20dfe34

Electrical / Breaker / MPCB

546.00 AED 546.0 AED 546.00 AED

546.00 AED

Not Available For Sale

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: usually 2-3 Business Days, once order is placed, actual lead time will be confirmed.

Attachments

TeSys GV motor circuit breaker, 3 poles (3P), 65A/690V, for 3-phase motor applications 30kW@400V. It provides a thermal-magnetic protection with a thermal setting range 48-65A, magnetic tripping at 15xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).


Specifications

Main

rangeTeSys Deca
TeSys Deca
product nameTeSys GV3
TeSys Deca
product or component typeMotor circuit breaker
device short nameGV3P
device applicationMotor protection
trip unit technologyThermal-magnetic

Complementary

poles description3P
network typeAC
utilisation categoryAC-3 conforming to IEC 60947-4-1
network frequency50/60 Hz conforming to IEC 60947-4-1
motor power kW55 kW at 690 V AC 50/60 Hz
45 kW at 500 V AC 50/60 Hz
30 kW at 400/415 V AC 50/60 Hz
breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control typeRotary handle
[In] rated current65 A
magnetic tripping current910 A
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current65 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
power dissipation per pole8 W
mechanical durability50000 cycles
electrical durability50000 cycles for AC-3 at 415 V In
rated dutyContinuous conforming to IEC 60947-4-1
phase failure sensitivityYes conforming to IEC 60947-4-1
suitability for isolationYes conforming to IEC 60947-1
width55 mm
Height132 mm
Depth136 mm
Net weight0.96 kg

Environment

StandardsEN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
product certificationsCCC
EAC
BV
LROS (Lloyds register of shipping)
DNV-GL
ABS
UL
CSA
UKCA
ATEX
IP degree of protectionIP20 conforming to IEC 60529
climatic withstandConforming to IACS E10
Ambient air temperature for storage-40…80 °C
fire resistance960 °C conforming to IEC 60695-2-11
ambient air temperature for operation-20…60 °C
operating altitude3000 m

Packing Units

Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height16.000 cm
Package 1 Width6.500 cm
Package 1 Length14.600 cm
Package 1 Weight1.016 kg
Unit Type of Package 2P06
Number of Units in Package 2120
Package 2 Height75.000 cm
Package 2 Width60.000 cm
Package 2 Length80.000 cm
Package 2 Weight134.920 kg