This Harmony RM17-TG relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase supply control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. The product monitors its own power supply, when the power supply is abnormal, the output relay de-energizes. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.  [RM17TG20]

Specifications

Main

Range of productHarmony Control Relays
Product or component type3-phase control relay
Relay typeControl relay
Product specific applicationFor 3-phase supply
Relay nameRM17TG
Relay monitored parametersPhase sequence
Phase failure detection (2 or more phase cut)
time delayWithout
Switching capacity in VA1250 VA
measurement range208...440 V voltage AC
Contacts type and composition2 C/O
[Uc] control circuit voltage208...440 V

Complementary

maximum switching voltage250 V AC
250 V DC
minimum switching current10 mA at 5 V DC
supply voltage limits183…484 V AC
Control circuit voltage limits- 12 % + 10 % Un
power consumption in VA0…22 VA at 400 V AC 50 Hz
voltage detection threshold< 100 V AC
Control circuit frequency50...60 Hz +/- 10 %
Output contacts2 C/O
Nominal output current5 A
measurement voltage limits183…484 V AC
delay at power up650 ms
voltage range183...484 V
response time<= 130 ms (in the event of a fault)
MarkingCE
overvoltage categoryIII conforming to IEC 60664-1
insulation resistance> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage400 V conforming to IEC 60664-1
Supply frequency50/60 Hz +/- 10 %
operating positionAny position without derating
connections - terminalsScrew terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
tightening torque0.6…1 N.m conforming to IEC 60947-1
Housing materialSelf-extinguishing plastic
local signallingLED (yellow) for relay ON
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability10000 cycles
Mechanical durability30000000 cycles
operating rate<= 360 operations/hour full load
utilisation categoryAC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
Safety reliability dataB10d = 850000
MTTFd = 924.6 years
Width17.5 mm
Net weight0.13 kg

Environment

electromagnetic compatibilityEmission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to EN/IEC 61000-6-2
StandardsEN/IEC 60255-1
Product certificationsGOST
C-Tick
UL
CSA
GL
Directives73/23/EEC - low voltage directive
89/336/EEC - electromagnetic compatibility
Ambient air temperature for storage-40…70 °C
ambient air temperature for operation-20…50 °C
relative humidity95 % at 55 °C conforming to IEC 60068-2-30
vibration resistance0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
shock resistance15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protectionIP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
pollution degree3 conforming to IEC 60664-1
dielectric test voltage2 kV, 1 min AC 50 Hz
non-dissipating shock wave4 kV